Electronics calculator

Free Wire size calculator

Enter your load current, run length, system voltage and allowed drop, and this calculator returns the minimum wire size (AWG) by the NEC circular-mil method — for copper or aluminum, single- or three-phase — with the actual voltage drop at that size, updated live, as you type.

InputsLive
Load current
A
One-way distance to load
ft
Source voltage
V
Allowed voltage dropNEC guidance: 3%
%
Conductor material
System phase
Result
Minimum wire size
8 AWG
Smallest standard conductor that keeps the drop within 3.00% — actual drop 2.60%.
Actual voltage drop3.13 V (2.60%)
Allowed drop3.60 V
Circular mils required14,333 cmil

Sizes for voltage drop only — also check ampacity and breaker rating against the NEC and a licensed electrician.

Results are estimates. Consult a professional.

How it's calculated

How the wire size calculator works

Long wire runs lose voltage to the resistance of the conductor, and a conductor that is too thin lets that loss grow until equipment underperforms. This calculator works backwards from a voltage-drop limit: you tell it the load current, the one-way distance, the system voltage, and the drop you are willing to accept, and it returns the smallest standard AWG conductor that stays inside that limit — then shows the actual drop you would get at that size.

CM = (k × K × L × I) / V_drop_allowed
k = 2 (single-phase) or √3 (three-phase)
V_drop_allowed = source_V × allowed% / 100
The circular-mil sizing method and the conductor cross-sections come from the National Electrical Code (NFPA 70), Chapter 9, Table 8 — Conductor Properties. The K values are the standard one-foot, one-circular-mil resistances of copper and aluminum.
The formula

The circular-mil sizing formula explained

Each input pushes the required conductor size in a direction you can reason about before you ever run the numbers. The bigger the cross-section a run demands, the thicker the wire — and a lower AWG number means a thicker wire.

Current and distance — they multiply

Current and one-way length sit together on top of the fraction, so they scale the requirement directly: double the current or double the distance and you double the circular mils you need. The factor of 2 (or √3 for three-phase) accounts for the full circuit path, not just the run out to the load.

Allowed drop — the budget you set

The allowed voltage drop sits on the bottom of the fraction, so a tighter budget demands a bigger conductor. Halving the allowed percentage roughly doubles the required circular mils. This is the lever you control: a 3% limit is stricter — and needs more copper — than a 5% limit.

The material constant K

K captures how resistive the metal is per foot per circular mil. Copper sits at 12.9 and aluminum at 21.2, so aluminum needs about 64% more cross-section to carry the same current the same distance with the same drop.

Round up, never down
The formula gives a minimum cross-section. Real conductors only come in standard sizes, so the calculator always rounds the requirement UP to the next AWG. Rounding down would push the drop over your limit.
Quick reference

AWG to circular-mil reference table

These are the standard copper and aluminum building-wire sizes the calculator chooses from, with their cross-sections in circular mils. A lower AWG number is a physically thicker wire; "1/0" through "4/0" (spoken "one-aught" to "four-aught") are larger than 1 AWG.

Wire size (AWG)Circular mils
14 AWG4,110
12 AWG6,530
10 AWG10,380
8 AWG16,510
6 AWG26,240
4 AWG41,740
2 AWG66,360
1 AWG83,690
1/0 AWG105,600
2/0 AWG133,100
3/0 AWG167,800
4/0 AWG211,600

Cross-sections per NEC Chapter 9, Table 8. The calculator picks the first size whose circular mils meet or exceed the requirement.

Example

A worked example using the wire size calculator

Example: a 20 A load 100 feet away on a 120 V circuit

Dana is running a single-phase 120 V branch circuit to a workshop subpanel 100 feet away that will draw about 20 amps. She wants to keep voltage drop within the NEC-recommended 3% using copper conductor, and needs to know the minimum wire size before pulling cable.

Step 1 — Find the voltage-drop budget

V_drop_allowed = 120 V × 3% = 3.6 V. That is the most the run may lose and still satisfy the 3% target.

Step 2 — Compute the required circular mils

CM = (2 × 12.9 × 100 × 20) ÷ 3.6 = 51,600 ÷ 3.6 = 14,333 circular mils. The factor is 2 because this is single-phase, and K = 12.9 for copper.

Step 3 — Round up to a standard size

10 AWG (10,380 cmil) is too small; the next size up, 8 AWG (16,510 cmil), clears the requirement. So 8 AWG copper is the minimum for voltage drop.

8 AWG copper — actual drop 3.13 V (2.60%)
At 8 AWG the real drop is 51,600 ÷ 16,510 = 3.13 V, which is 2.60% of 120 V — comfortably inside the 3% target with a little margin. This matches the calculator's default result exactly.
The standard

The NEC 3% voltage-drop guidance

The National Electrical Code does not make voltage drop a hard rule for most circuits — it appears as a recommendation in informational notes rather than a mandatory limit. The widely used figures are 3% on a branch circuit and 5% total across feeder plus branch combined.

  • 3% on the branch circuit — the run from the last panel out to the load (NEC 210.19(A) informational note).
  • 5% total — feeder plus branch combined, from the service to the load (NEC 215.2(A) informational note).
  • Sensitive or motor loads — some equipment and local rules call for tighter limits; check the equipment listing.

Why it matters: voltage at the load is what actually powers equipment. Excessive drop dims lighting, cuts motor torque and starting current, and wastes energy as heat in the conductor. Sizing to 3% keeps equipment within its rated voltage and leaves headroom for the feeder's share of the budget.

Material

Copper vs aluminum conductors

Aluminum is cheaper and lighter than copper but more resistive, so it needs a larger cross-section for the same job. In the formula this shows up as the K constant: 12.9 for copper versus 21.2 for aluminum — about 64% higher resistance per circular mil.

PropertyCopperAluminum
K (Ω·cmil/ft)12.921.2
Relative size for same dropBaseline≈ 64% more cross-section
Typical sizing rule of thumbRoughly two AWG sizes larger
Cost / weightHigherLower

For the same current, distance and drop, aluminum lands on a noticeably larger wire size than copper.

Aluminum is common for large feeders and service entrances where the cost saving is significant, while copper dominates branch circuits. Aluminum terminations need listed connectors and anti-oxidant compound; follow the equipment and code requirements for the metal you choose.

Don't skip this

Voltage drop is only half the job — ampacity comes first

This calculator sizes a conductor for voltage drop only. Before that, every conductor must also meet its ampacity — the maximum current it can carry without overheating — and be protected by a correctly rated breaker or fuse. Ampacity is a separate NEC requirement (Table 310.16), not something this tool checks.

The two requirements work together: pick the larger of the ampacity-required size and the voltage-drop-required size. On short runs ampacity usually governs; on long runs voltage drop often forces a bigger conductor than ampacity alone would. Both must be satisfied, along with derating for temperature and conductor bundling, and the overcurrent device must match the conductor.

Always size for both
A wire that passes voltage drop can still be unsafe if it is too small for the current. Confirm the ampacity from the NEC table and the breaker rating for your conductor and installation before pulling cable.
Accuracy & safety

Safety, accuracy and limits

The arithmetic is exact. For the current, distance, voltage and drop you enter, the calculator computes the precise circular-mil requirement and selects the smallest standard AWG that meets it, then reports the true drop at that size to full precision.

Real installations carry factors the formula does not: ambient temperature changes conductor resistance, large alternating-current conductors add reactance the DC method ignores, and bundled or high-temperature runs require derating. The circular-mil method is the standard approximation for typical 60 Hz building circuits and matches the voltage-drop calculator's results, but it is an estimate, not a code sign-off.

Consult the NEC and a licensed electrician
Use this result as a design starting point. Final conductor sizing must satisfy the current National Electrical Code (and any local amendments) for ampacity, voltage drop, derating and overcurrent protection — verify it with a licensed electrician before wiring.
Questions

Frequently asked questions about the free Wire size calculator

A wire size calculator is a free online tool that helps you find the minimum wire size (AWG) to hold voltage drop within a target percent — by the NEC circular-mil method, for copper or aluminum, single- or three-phase. Size a conductor so its voltage drop stays within a limit. The NEC circular-mil method turns the load and run length into a minimum cross-section, then rounds up to a standard AWG. It runs entirely in your browser with instant results and no sign-up.
By the NEC circular-mil method, CM = (2 × 12.9 × 100 × 20) / (120 × 3%) = 14,333 circular mils. The next standard size up is 8 AWG copper (16,510 cmil), which gives an actual drop of about 3.13 V, or 2.60% — inside the 3% target. This sizes for voltage drop only; also confirm ampacity and breaker rating.
It computes the minimum cross-section in circular mils needed to stay within your allowed voltage drop, then rounds up to the smallest standard AWG whose area meets or exceeds that — never down, which would push the drop over your limit.
Aluminum is more resistive: its constant K is 21.2 versus 12.9 for copper, about 64% higher. For the same current, distance and drop it needs roughly 64% more cross-section — often about two AWG sizes larger.
No. It sizes for voltage drop only. Every conductor must also meet its ampacity (NEC Table 310.16) and be protected by a correctly rated breaker. Use the larger of the ampacity-required and voltage-drop-required size — on long runs voltage drop often governs, on short runs ampacity does.
The NEC recommends, in informational notes, a maximum of 3% drop on a branch circuit and 5% total across feeder plus branch combined. These are recommendations rather than mandatory limits for most circuits, but they keep equipment within its rated voltage.
About

About this wire size calculator

This wire size calculator runs entirely in your browser using the NEC Chapter 9 circular-mil method. Enter the load current, one-way distance, source voltage and the voltage drop you'll allow, pick copper or aluminum and single- or three-phase, and it returns the smallest standard AWG that stays within your limit plus the actual drop at that size — computed locally and updated as you type. It sizes for voltage drop only; ampacity and breaker rating are separate NEC requirements.

It pairs with the voltage drop calculator (its inverse) and Ohm’s law. Browse more electronics calculators or the full calculator library.

Want a calculator built for your business?

Customize any of our 400+ tools to match your brand, or commission a new one tailored to how your business actually calculates — pricing, payroll, quotes, anything. Deployed on your domain, math runs in your visitors' browsers.